Summary
A vulnerability has been identified in APOGEE PXC+TALON TC Series (BACnet) (All versions). Affected devices start sending unsolicited BACnet broadcast messages after processing a specific BACnet createObject request. This could allow an attacker residing in the same BACnet network to send a specially crafted message that results in a partial denial of service condition of the targeted device, and potentially reduce the availability of BACnet network. A power cycle is required to restore the device's normal operation.
References
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | APOGEE PXC+TALON TC Series (BACnet) |
Version: 0 < * |
{ "containers": { "adp": [ { "metrics": [ { "other": { "content": { "id": "CVE-2025-40555", "options": [ { "Exploitation": "none" }, { "Automatable": "no" }, { "Technical Impact": "partial" } ], "role": "CISA Coordinator", "timestamp": "2025-05-13T13:23:44.449721Z", "version": "2.0.3" }, "type": "ssvc" } } ], "providerMetadata": { "dateUpdated": "2025-05-13T13:25:06.076Z", "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0", "shortName": "CISA-ADP" }, "title": "CISA ADP Vulnrichment" } ], "cna": { "affected": [ { "defaultStatus": "unknown", "product": "APOGEE PXC+TALON TC Series (BACnet)", "vendor": "Siemens", "versions": [ { "lessThan": "*", "status": "affected", "version": "0", "versionType": "custom" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in APOGEE PXC+TALON TC Series (BACnet) (All versions). Affected devices start sending unsolicited BACnet broadcast messages after processing a specific BACnet createObject request. This could allow an attacker residing in the same BACnet network to send a specially crafted message that results in a partial denial of service condition of the targeted device, and potentially reduce the availability of BACnet network. A power cycle is required to restore the device\u0027s normal operation." } ], "metrics": [ { "cvssV3_1": { "baseScore": 4.7, "baseSeverity": "MEDIUM", "vectorString": "CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:L", "version": "3.1" } }, { "cvssV4_0": { "baseScore": 5.3, "baseSeverity": "MEDIUM", "vectorString": "CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:L/SC:N/SI:N/SA:L", "version": "4.0" } } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-440", "description": "CWE-440: Expected Behavior Violation", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2025-05-13T09:38:50.440Z", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "url": "https://cert-portal.siemens.com/productcert/html/ssa-718393.html" } ] } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2025-40555", "datePublished": "2025-05-13T09:38:50.440Z", "dateReserved": "2025-04-16T08:20:17.029Z", "dateUpdated": "2025-05-13T13:25:06.076Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }