Vulnerabilites related to Siemens - CPCI85 Central Processing/Communication
CVE-2024-39601 (GCVE-0-2024-39601)
Vulnerability from cvelistv5
Published
2024-07-22 13:54
Modified
2024-08-02 04:26
CWE
  • CWE-306 - Missing Authentication for Critical Function
Summary
A vulnerability has been identified in CPCI85 Central Processing/Communication (All versions < V5.40), SICORE Base system (All versions < V1.4.0). Affected devices allow a remote authenticated user or an unauthenticated user with physical access to downgrade the firmware of the device. This could allow an attacker to downgrade the device to older versions with known vulnerabilities.
Show details on NVD website


{
  "containers": {
    "adp": [
      {
        "metrics": [
          {
            "other": {
              "content": {
                "id": "CVE-2024-39601",
                "options": [
                  {
                    "Exploitation": "none"
                  },
                  {
                    "Automatable": "no"
                  },
                  {
                    "Technical Impact": "partial"
                  }
                ],
                "role": "CISA Coordinator",
                "timestamp": "2024-07-23T13:22:20.845382Z",
                "version": "2.0.3"
              },
              "type": "ssvc"
            }
          }
        ],
        "providerMetadata": {
          "dateUpdated": "2024-07-23T13:22:30.117Z",
          "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
          "shortName": "CISA-ADP"
        },
        "title": "CISA ADP Vulnrichment"
      },
      {
        "providerMetadata": {
          "dateUpdated": "2024-08-02T04:26:15.934Z",
          "orgId": "af854a3a-2127-422b-91ae-364da2661108",
          "shortName": "CVE"
        },
        "references": [
          {
            "tags": [
              "x_transferred"
            ],
            "url": "https://cert-portal.siemens.com/productcert/html/ssa-071402.html"
          }
        ],
        "title": "CVE Program Container"
      }
    ],
    "cna": {
      "affected": [
        {
          "defaultStatus": "unknown",
          "product": "CPCI85 Central Processing/Communication",
          "vendor": "Siemens",
          "versions": [
            {
              "lessThan": "V5.40",
              "status": "affected",
              "version": "0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unknown",
          "product": "SICORE Base system",
          "vendor": "Siemens",
          "versions": [
            {
              "lessThan": "V1.4.0",
              "status": "affected",
              "version": "0",
              "versionType": "custom"
            }
          ]
        }
      ],
      "descriptions": [
        {
          "lang": "en",
          "value": "A vulnerability has been identified in CPCI85 Central Processing/Communication (All versions \u003c V5.40), SICORE Base system (All versions \u003c V1.4.0). Affected devices allow a remote authenticated user or an unauthenticated user with physical access to downgrade the firmware of the device. This could allow an attacker to downgrade the device to older versions with known vulnerabilities."
        }
      ],
      "metrics": [
        {
          "cvssV3_1": {
            "baseScore": 6.5,
            "baseSeverity": "MEDIUM",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:N",
            "version": "3.1"
          }
        },
        {
          "cvssV4_0": {
            "baseScore": 7.1,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:N/VI:H/VA:N/SC:N/SI:N/SA:N",
            "version": "4.0"
          }
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "cweId": "CWE-306",
              "description": "CWE-306: Missing Authentication for Critical Function",
              "lang": "en",
              "type": "CWE"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2024-07-22T13:54:50.768Z",
        "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77",
        "shortName": "siemens"
      },
      "references": [
        {
          "url": "https://cert-portal.siemens.com/productcert/html/ssa-071402.html"
        }
      ]
    }
  },
  "cveMetadata": {
    "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77",
    "assignerShortName": "siemens",
    "cveId": "CVE-2024-39601",
    "datePublished": "2024-07-22T13:54:50.768Z",
    "dateReserved": "2024-06-26T13:43:16.586Z",
    "dateUpdated": "2024-08-02T04:26:15.934Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.1"
}

CVE-2024-31484 (GCVE-0-2024-31484)
Vulnerability from cvelistv5
Published
2024-05-14 10:02
Modified
2025-02-13 17:47
CWE
  • CWE-170 - Improper Null Termination
Summary
A vulnerability has been identified in CPC80 Central Processing/Communication (All versions < V16.41), CPCI85 Central Processing/Communication (All versions < V5.30), CPCX26 Central Processing/Communication (All versions < V06.02), ETA4 Ethernet Interface IEC60870-5-104 (All versions < V10.46), ETA5 Ethernet Int. 1x100TX IEC61850 Ed.2 (All versions < V03.27), PCCX26 Ax 1703 PE, Contr, Communication Element (All versions < V06.05). The affected devices contain an improper null termination vulnerability while parsing a specific HTTP header. This could allow an attacker to execute code in the context of the current process or lead to denial of service condition.
Show details on NVD website


{
  "containers": {
    "adp": [
      {
        "affected": [
          {
            "cpes": [
              "cpe:2.3:a:siemens:cpc80_central_processing\\/communication:16.41:*:*:*:*:*:*:*"
            ],
            "defaultStatus": "unknown",
            "product": "cpc80_central_processing\\/communication",
            "vendor": "siemens",
            "versions": [
              {
                "lessThan": "16.41",
                "status": "affected",
                "version": "0",
                "versionType": "custom"
              }
            ]
          },
          {
            "cpes": [
              "cpe:2.3:a:siemens:cpci85_central_processing\\/communication:5.30:*:*:*:*:*:*:*"
            ],
            "defaultStatus": "unknown",
            "product": "cpci85_central_processing\\/communication",
            "vendor": "siemens",
            "versions": [
              {
                "lessThan": "5.30",
                "status": "affected",
                "version": "0",
                "versionType": "custom"
              }
            ]
          }
        ],
        "metrics": [
          {
            "other": {
              "content": {
                "id": "CVE-2024-31484",
                "options": [
                  {
                    "Exploitation": "none"
                  },
                  {
                    "Automatable": "no"
                  },
                  {
                    "Technical Impact": "total"
                  }
                ],
                "role": "CISA Coordinator",
                "timestamp": "2024-05-28T19:54:51.490746Z",
                "version": "2.0.3"
              },
              "type": "ssvc"
            }
          }
        ],
        "providerMetadata": {
          "dateUpdated": "2024-06-04T17:36:20.360Z",
          "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
          "shortName": "CISA-ADP"
        },
        "title": "CISA ADP Vulnrichment"
      },
      {
        "providerMetadata": {
          "dateUpdated": "2024-11-27T21:02:39.703Z",
          "orgId": "af854a3a-2127-422b-91ae-364da2661108",
          "shortName": "CVE"
        },
        "references": [
          {
            "tags": [
              "x_transferred"
            ],
            "url": "https://cert-portal.siemens.com/productcert/html/ssa-871704.html"
          },
          {
            "tags": [
              "x_transferred"
            ],
            "url": "https://cert-portal.siemens.com/productcert/html/ssa-620338.html"
          },
          {
            "tags": [
              "x_transferred"
            ],
            "url": "http://seclists.org/fulldisclosure/2024/Jul/4"
          },
          {
            "url": "http://seclists.org/fulldisclosure/2024/Nov/18"
          }
        ],
        "title": "CVE Program Container"
      }
    ],
    "cna": {
      "affected": [
        {
          "defaultStatus": "unknown",
          "product": "CPC80 Central Processing/Communication",
          "vendor": "Siemens",
          "versions": [
            {
              "lessThan": "V16.41",
              "status": "affected",
              "version": "0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unknown",
          "product": "CPCI85 Central Processing/Communication",
          "vendor": "Siemens",
          "versions": [
            {
              "lessThan": "V5.30",
              "status": "affected",
              "version": "0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unknown",
          "product": "CPCX26 Central Processing/Communication",
          "vendor": "Siemens",
          "versions": [
            {
              "lessThan": "V06.02",
              "status": "affected",
              "version": "0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unknown",
          "product": "ETA4 Ethernet Interface IEC60870-5-104",
          "vendor": "Siemens",
          "versions": [
            {
              "lessThan": "V10.46",
              "status": "affected",
              "version": "0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unknown",
          "product": "ETA5 Ethernet Int. 1x100TX IEC61850 Ed.2",
          "vendor": "Siemens",
          "versions": [
            {
              "lessThan": "V03.27",
              "status": "affected",
              "version": "0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unknown",
          "product": "PCCX26 Ax 1703 PE, Contr, Communication Element",
          "vendor": "Siemens",
          "versions": [
            {
              "lessThan": "V06.05",
              "status": "affected",
              "version": "0",
              "versionType": "custom"
            }
          ]
        }
      ],
      "descriptions": [
        {
          "lang": "en",
          "value": "A vulnerability has been identified in CPC80 Central Processing/Communication (All versions \u003c V16.41), CPCI85 Central Processing/Communication (All versions \u003c V5.30), CPCX26 Central Processing/Communication (All versions \u003c V06.02), ETA4 Ethernet Interface IEC60870-5-104 (All versions \u003c V10.46), ETA5 Ethernet Int. 1x100TX IEC61850 Ed.2 (All versions \u003c V03.27), PCCX26 Ax 1703 PE, Contr, Communication Element (All versions \u003c V06.05). The affected devices contain an improper null termination vulnerability while parsing a specific HTTP header. This could allow an attacker to execute code in the context of the current process or lead to denial of service condition."
        }
      ],
      "metrics": [
        {
          "cvssV3_1": {
            "baseScore": 7.8,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H",
            "version": "3.1"
          }
        },
        {
          "cvssV4_0": {
            "baseScore": 7.3,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:4.0/AV:L/AC:H/AT:N/PR:N/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N",
            "version": "4.0"
          }
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "cweId": "CWE-170",
              "description": "CWE-170: Improper Null Termination",
              "lang": "en",
              "type": "CWE"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2024-07-04T06:06:04.302Z",
        "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77",
        "shortName": "siemens"
      },
      "references": [
        {
          "url": "https://cert-portal.siemens.com/productcert/html/ssa-871704.html"
        },
        {
          "url": "https://cert-portal.siemens.com/productcert/html/ssa-620338.html"
        },
        {
          "url": "http://seclists.org/fulldisclosure/2024/Jul/4"
        }
      ]
    }
  },
  "cveMetadata": {
    "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77",
    "assignerShortName": "siemens",
    "cveId": "CVE-2024-31484",
    "datePublished": "2024-05-14T10:02:23.871Z",
    "dateReserved": "2024-04-04T11:43:06.066Z",
    "dateUpdated": "2025-02-13T17:47:58.073Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.1"
}

CVE-2024-31485 (GCVE-0-2024-31485)
Vulnerability from cvelistv5
Published
2024-05-14 10:02
Modified
2025-02-13 17:47
CWE
  • CWE-77 - Improper Neutralization of Special Elements used in a Command ('Command Injection')
Summary
A vulnerability has been identified in CPCI85 Central Processing/Communication (All versions < V5.30), SICORE Base system (All versions < V1.3.0). The web interface of affected devices is vulnerable to command injection due to missing server side input sanitation. This could allow an authenticated privileged remote attacker to execute arbitrary code with root privileges.
Show details on NVD website


{
  "containers": {
    "adp": [
      {
        "affected": [
          {
            "cpes": [
              "cpe:2.3:o:siemens:sicore_base_system:*:*:*:*:*:*:*:*"
            ],
            "defaultStatus": "unknown",
            "product": "sicore_base_system",
            "vendor": "siemens",
            "versions": [
              {
                "lessThan": "V1.3.0",
                "status": "affected",
                "version": "0",
                "versionType": "custom"
              }
            ]
          },
          {
            "cpes": [
              "cpe:2.3:o:siemens:cpci85_firmware:*:*:*:*:*:*:*:*"
            ],
            "defaultStatus": "unknown",
            "product": "cpci85_firmware",
            "vendor": "siemens",
            "versions": [
              {
                "lessThan": "V5.30",
                "status": "affected",
                "version": "0",
                "versionType": "custom"
              }
            ]
          }
        ],
        "metrics": [
          {
            "other": {
              "content": {
                "id": "CVE-2024-31485",
                "options": [
                  {
                    "Exploitation": "poc"
                  },
                  {
                    "Automatable": "no"
                  },
                  {
                    "Technical Impact": "total"
                  }
                ],
                "role": "CISA Coordinator",
                "timestamp": "2024-07-09T18:48:59.342484Z",
                "version": "2.0.3"
              },
              "type": "ssvc"
            }
          }
        ],
        "providerMetadata": {
          "dateUpdated": "2024-07-24T16:56:47.966Z",
          "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
          "shortName": "CISA-ADP"
        },
        "title": "CISA ADP Vulnrichment"
      },
      {
        "providerMetadata": {
          "dateUpdated": "2024-08-02T01:52:57.134Z",
          "orgId": "af854a3a-2127-422b-91ae-364da2661108",
          "shortName": "CVE"
        },
        "references": [
          {
            "tags": [
              "x_transferred"
            ],
            "url": "https://cert-portal.siemens.com/productcert/html/ssa-871704.html"
          },
          {
            "tags": [
              "x_transferred"
            ],
            "url": "http://seclists.org/fulldisclosure/2024/Jul/4"
          }
        ],
        "title": "CVE Program Container"
      }
    ],
    "cna": {
      "affected": [
        {
          "defaultStatus": "unknown",
          "product": "CPCI85 Central Processing/Communication",
          "vendor": "Siemens",
          "versions": [
            {
              "lessThan": "V5.30",
              "status": "affected",
              "version": "0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unknown",
          "product": "SICORE Base system",
          "vendor": "Siemens",
          "versions": [
            {
              "lessThan": "V1.3.0",
              "status": "affected",
              "version": "0",
              "versionType": "custom"
            }
          ]
        }
      ],
      "descriptions": [
        {
          "lang": "en",
          "value": "A vulnerability has been identified in CPCI85 Central Processing/Communication (All versions \u003c V5.30), SICORE Base system (All versions \u003c V1.3.0). The web interface of affected devices is vulnerable to command injection due to missing server side input sanitation. This could allow an authenticated privileged remote attacker to execute arbitrary code with root privileges."
        }
      ],
      "metrics": [
        {
          "cvssV3_1": {
            "baseScore": 7.2,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.1"
          }
        },
        {
          "cvssV4_0": {
            "baseScore": 8.6,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:4.0/AV:N/AC:L/AT:N/PR:H/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N",
            "version": "4.0"
          }
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "cweId": "CWE-77",
              "description": "CWE-77: Improper Neutralization of Special Elements used in a Command (\u0027Command Injection\u0027)",
              "lang": "en",
              "type": "CWE"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2024-07-04T06:06:06.143Z",
        "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77",
        "shortName": "siemens"
      },
      "references": [
        {
          "url": "https://cert-portal.siemens.com/productcert/html/ssa-871704.html"
        },
        {
          "url": "http://seclists.org/fulldisclosure/2024/Jul/4"
        }
      ]
    }
  },
  "cveMetadata": {
    "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77",
    "assignerShortName": "siemens",
    "cveId": "CVE-2024-31485",
    "datePublished": "2024-05-14T10:02:25.052Z",
    "dateReserved": "2024-04-04T11:43:06.066Z",
    "dateUpdated": "2025-02-13T17:47:58.693Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.1"
}

CVE-2024-53832 (GCVE-0-2024-53832)
Vulnerability from cvelistv5
Published
2024-12-10 13:54
Modified
2024-12-10 17:17
CWE
  • CWE-522 - Insufficiently Protected Credentials
Summary
A vulnerability has been identified in CPCI85 Central Processing/Communication (All versions < V05.30). The affected devices contain a secure element which is connected via an unencrypted SPI bus. This could allow an attacker with physical access to the SPI bus to observe the password used for the secure element authentication, and then use the secure element as an oracle to decrypt all encrypted update files.
Impacted products
Show details on NVD website


{
  "containers": {
    "adp": [
      {
        "metrics": [
          {
            "other": {
              "content": {
                "id": "CVE-2024-53832",
                "options": [
                  {
                    "Exploitation": "none"
                  },
                  {
                    "Automatable": "no"
                  },
                  {
                    "Technical Impact": "partial"
                  }
                ],
                "role": "CISA Coordinator",
                "timestamp": "2024-12-10T15:16:55.369787Z",
                "version": "2.0.3"
              },
              "type": "ssvc"
            }
          }
        ],
        "providerMetadata": {
          "dateUpdated": "2024-12-10T17:17:37.372Z",
          "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
          "shortName": "CISA-ADP"
        },
        "title": "CISA ADP Vulnrichment"
      }
    ],
    "cna": {
      "affected": [
        {
          "defaultStatus": "unknown",
          "product": "CPCI85 Central Processing/Communication",
          "vendor": "Siemens",
          "versions": [
            {
              "lessThan": "V05.30",
              "status": "affected",
              "version": "0",
              "versionType": "custom"
            }
          ]
        }
      ],
      "descriptions": [
        {
          "lang": "en",
          "value": "A vulnerability has been identified in CPCI85 Central Processing/Communication (All versions \u003c V05.30). The affected devices contain a secure element which is connected via an unencrypted SPI bus. This could allow an attacker with physical access to the SPI bus to observe the password used for the secure element authentication, and then use the secure element as an oracle to decrypt all encrypted update files."
        }
      ],
      "metrics": [
        {
          "cvssV3_1": {
            "baseScore": 4.6,
            "baseSeverity": "MEDIUM",
            "vectorString": "CVSS:3.1/AV:P/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N",
            "version": "3.1"
          }
        },
        {
          "cvssV4_0": {
            "baseScore": 5.1,
            "baseSeverity": "MEDIUM",
            "vectorString": "CVSS:4.0/AV:P/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N",
            "version": "4.0"
          }
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "cweId": "CWE-522",
              "description": "CWE-522: Insufficiently Protected Credentials",
              "lang": "en",
              "type": "CWE"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2024-12-10T13:54:14.682Z",
        "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77",
        "shortName": "siemens"
      },
      "references": [
        {
          "url": "https://cert-portal.siemens.com/productcert/html/ssa-128393.html"
        }
      ]
    }
  },
  "cveMetadata": {
    "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77",
    "assignerShortName": "siemens",
    "cveId": "CVE-2024-53832",
    "datePublished": "2024-12-10T13:54:14.682Z",
    "dateReserved": "2024-11-22T14:39:32.052Z",
    "dateUpdated": "2024-12-10T17:17:37.372Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.1"
}

CVE-2024-37998 (GCVE-0-2024-37998)
Vulnerability from cvelistv5
Published
2024-07-22 13:54
Modified
2024-08-02 04:04
CWE
  • CWE-620 - Unverified Password Change
Summary
A vulnerability has been identified in CPCI85 Central Processing/Communication (All versions < V5.40), SICORE Base system (All versions < V1.4.0). The password of administrative accounts of the affected applications can be reset without requiring the knowledge of the current password, given the auto login is enabled. This could allow an unauthorized attacker to obtain administrative access of the affected applications.
Show details on NVD website


{
  "containers": {
    "adp": [
      {
        "affected": [
          {
            "cpes": [
              "cpe:2.3:o:siemens:cpci85_firmware:*:*:*:*:*:*:*:*"
            ],
            "defaultStatus": "unknown",
            "product": "cpci85_firmware",
            "vendor": "siemens",
            "versions": [
              {
                "lessThan": "5.40",
                "status": "affected",
                "version": "0",
                "versionType": "custom"
              }
            ]
          },
          {
            "cpes": [
              "cpe:2.3:o:siemens:sicore_base_system:*:*:*:*:*:*:*:*"
            ],
            "defaultStatus": "unknown",
            "product": "sicore_base_system",
            "vendor": "siemens",
            "versions": [
              {
                "lessThan": "1.4.0",
                "status": "affected",
                "version": "0",
                "versionType": "custom"
              }
            ]
          }
        ],
        "metrics": [
          {
            "other": {
              "content": {
                "id": "CVE-2024-37998",
                "options": [
                  {
                    "Exploitation": "none"
                  },
                  {
                    "Automatable": "yes"
                  },
                  {
                    "Technical Impact": "total"
                  }
                ],
                "role": "CISA Coordinator",
                "timestamp": "2024-07-24T16:50:47.506327Z",
                "version": "2.0.3"
              },
              "type": "ssvc"
            }
          }
        ],
        "providerMetadata": {
          "dateUpdated": "2024-07-24T16:56:51.191Z",
          "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
          "shortName": "CISA-ADP"
        },
        "title": "CISA ADP Vulnrichment"
      },
      {
        "providerMetadata": {
          "dateUpdated": "2024-08-02T04:04:24.632Z",
          "orgId": "af854a3a-2127-422b-91ae-364da2661108",
          "shortName": "CVE"
        },
        "references": [
          {
            "tags": [
              "x_transferred"
            ],
            "url": "https://cert-portal.siemens.com/productcert/html/ssa-071402.html"
          }
        ],
        "title": "CVE Program Container"
      }
    ],
    "cna": {
      "affected": [
        {
          "defaultStatus": "unknown",
          "product": "CPCI85 Central Processing/Communication",
          "vendor": "Siemens",
          "versions": [
            {
              "lessThan": "V5.40",
              "status": "affected",
              "version": "0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unknown",
          "product": "SICORE Base system",
          "vendor": "Siemens",
          "versions": [
            {
              "lessThan": "V1.4.0",
              "status": "affected",
              "version": "0",
              "versionType": "custom"
            }
          ]
        }
      ],
      "descriptions": [
        {
          "lang": "en",
          "value": "A vulnerability has been identified in CPCI85 Central Processing/Communication (All versions \u003c V5.40), SICORE Base system (All versions \u003c V1.4.0). The password of administrative accounts of the affected applications can be reset without requiring the knowledge of the current password, given the auto login is enabled. This could allow an unauthorized attacker to obtain administrative access of the affected applications."
        }
      ],
      "metrics": [
        {
          "cvssV3_1": {
            "baseScore": 9.8,
            "baseSeverity": "CRITICAL",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.1"
          }
        },
        {
          "cvssV4_0": {
            "baseScore": 9.3,
            "baseSeverity": "CRITICAL",
            "vectorString": "CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N",
            "version": "4.0"
          }
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "cweId": "CWE-620",
              "description": "CWE-620: Unverified Password Change",
              "lang": "en",
              "type": "CWE"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2024-07-22T13:54:49.501Z",
        "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77",
        "shortName": "siemens"
      },
      "references": [
        {
          "url": "https://cert-portal.siemens.com/productcert/html/ssa-071402.html"
        }
      ]
    }
  },
  "cveMetadata": {
    "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77",
    "assignerShortName": "siemens",
    "cveId": "CVE-2024-37998",
    "datePublished": "2024-07-22T13:54:49.501Z",
    "dateReserved": "2024-06-11T08:32:52.184Z",
    "dateUpdated": "2024-08-02T04:04:24.632Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.1"
}