CVE-2020-6988 (GCVE-0-2020-6988)
Vulnerability from cvelistv5
Published
2020-03-16 15:38
Modified
2024-08-04 09:18
Severity ?
CWE
  • CWE-603 - USE OF CLIENT-SIDE AUTHENTICATION
Summary
Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, A remote, unauthenticated attacker can send a request from the RSLogix 500 software to the victim’s MicroLogix controller. The controller will then respond to the client with used password values to authenticate the user on the client-side. This method of authentication may allow an attacker to bypass authentication altogether, disclose sensitive information, or leak credentials.
References
Impacted products
Vendor Product Version
n/a Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior Version: Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior
Show details on NVD website


{
  "containers": {
    "adp": [
      {
        "providerMetadata": {
          "dateUpdated": "2024-08-04T09:18:02.514Z",
          "orgId": "af854a3a-2127-422b-91ae-364da2661108",
          "shortName": "CVE"
        },
        "references": [
          {
            "tags": [
              "x_refsource_MISC",
              "x_transferred"
            ],
            "url": "https://www.us-cert.gov/ics/advisories/icsa-20-070-06"
          }
        ],
        "title": "CVE Program Container"
      }
    ],
    "cna": {
      "affected": [
        {
          "product": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior",
          "vendor": "n/a",
          "versions": [
            {
              "status": "affected",
              "version": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior"
            }
          ]
        }
      ],
      "descriptions": [
        {
          "lang": "en",
          "value": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, A remote, unauthenticated attacker can send a request from the RSLogix 500 software to the victim\u2019s MicroLogix controller. The controller will then respond to the client with used password values to authenticate the user on the client-side. This method of authentication may allow an attacker to bypass authentication altogether, disclose sensitive information, or leak credentials."
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "cweId": "CWE-603",
              "description": "USE OF CLIENT-SIDE AUTHENTICATION CWE-603",
              "lang": "en",
              "type": "CWE"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2020-03-16T15:38:36",
        "orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
        "shortName": "icscert"
      },
      "references": [
        {
          "tags": [
            "x_refsource_MISC"
          ],
          "url": "https://www.us-cert.gov/ics/advisories/icsa-20-070-06"
        }
      ],
      "x_legacyV4Record": {
        "CVE_data_meta": {
          "ASSIGNER": "ics-cert@hq.dhs.gov",
          "ID": "CVE-2020-6988",
          "STATE": "PUBLIC"
        },
        "affects": {
          "vendor": {
            "vendor_data": [
              {
                "product": {
                  "product_data": [
                    {
                      "product_name": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior",
                      "version": {
                        "version_data": [
                          {
                            "version_value": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior"
                          }
                        ]
                      }
                    }
                  ]
                },
                "vendor_name": "n/a"
              }
            ]
          }
        },
        "data_format": "MITRE",
        "data_type": "CVE",
        "data_version": "4.0",
        "description": {
          "description_data": [
            {
              "lang": "eng",
              "value": "Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, A remote, unauthenticated attacker can send a request from the RSLogix 500 software to the victim\u2019s MicroLogix controller. The controller will then respond to the client with used password values to authenticate the user on the client-side. This method of authentication may allow an attacker to bypass authentication altogether, disclose sensitive information, or leak credentials."
            }
          ]
        },
        "problemtype": {
          "problemtype_data": [
            {
              "description": [
                {
                  "lang": "eng",
                  "value": "USE OF CLIENT-SIDE AUTHENTICATION CWE-603"
                }
              ]
            }
          ]
        },
        "references": {
          "reference_data": [
            {
              "name": "https://www.us-cert.gov/ics/advisories/icsa-20-070-06",
              "refsource": "MISC",
              "url": "https://www.us-cert.gov/ics/advisories/icsa-20-070-06"
            }
          ]
        }
      }
    }
  },
  "cveMetadata": {
    "assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
    "assignerShortName": "icscert",
    "cveId": "CVE-2020-6988",
    "datePublished": "2020-03-16T15:38:36",
    "dateReserved": "2020-01-14T00:00:00",
    "dateUpdated": "2024-08-04T09:18:02.514Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.1",
  "vulnerability-lookup:meta": {
    "nvd": "{\"cve\":{\"id\":\"CVE-2020-6988\",\"sourceIdentifier\":\"ics-cert@hq.dhs.gov\",\"published\":\"2020-03-16T16:15:14.767\",\"lastModified\":\"2024-11-21T05:36:26.567\",\"vulnStatus\":\"Modified\",\"cveTags\":[],\"descriptions\":[{\"lang\":\"en\",\"value\":\"Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, A remote, unauthenticated attacker can send a request from the RSLogix 500 software to the victim\u2019s MicroLogix controller. The controller will then respond to the client with used password values to authenticate the user on the client-side. This method of authentication may allow an attacker to bypass authentication altogether, disclose sensitive information, or leak credentials.\"},{\"lang\":\"es\",\"value\":\"Rockwell Automation MicroLogix 1400 Controllers Series B versiones  v21.001 y anteriores, Series A, todas las versiones, MicroLogix 1100 Controller, todas las versiones, RSLogix 500 Software versiones v12.001 y anteriores, un atacante no autenticado remoto puede enviar una petici\u00f3n desde el software RSLogix 500 hacia el controlador MicroLogix de la v\u00edctima. El controlador responder\u00e1 al cliente con los valores de contrase\u00f1a usados para autenticar al usuario en el lado del cliente. Este m\u00e9todo de autenticaci\u00f3n puede permitir a un atacante omitir la autenticaci\u00f3n por completo, revelar informaci\u00f3n confidencial o filtrar credenciales.\"}],\"metrics\":{\"cvssMetricV31\":[{\"source\":\"nvd@nist.gov\",\"type\":\"Primary\",\"cvssData\":{\"version\":\"3.1\",\"vectorString\":\"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N\",\"baseScore\":7.5,\"baseSeverity\":\"HIGH\",\"attackVector\":\"NETWORK\",\"attackComplexity\":\"LOW\",\"privilegesRequired\":\"NONE\",\"userInteraction\":\"NONE\",\"scope\":\"UNCHANGED\",\"confidentialityImpact\":\"HIGH\",\"integrityImpact\":\"NONE\",\"availabilityImpact\":\"NONE\"},\"exploitabilityScore\":3.9,\"impactScore\":3.6}],\"cvssMetricV2\":[{\"source\":\"nvd@nist.gov\",\"type\":\"Primary\",\"cvssData\":{\"version\":\"2.0\",\"vectorString\":\"AV:N/AC:L/Au:N/C:P/I:N/A:N\",\"baseScore\":5.0,\"accessVector\":\"NETWORK\",\"accessComplexity\":\"LOW\",\"authentication\":\"NONE\",\"confidentialityImpact\":\"PARTIAL\",\"integrityImpact\":\"NONE\",\"availabilityImpact\":\"NONE\"},\"baseSeverity\":\"MEDIUM\",\"exploitabilityScore\":10.0,\"impactScore\":2.9,\"acInsufInfo\":false,\"obtainAllPrivilege\":false,\"obtainUserPrivilege\":false,\"obtainOtherPrivilege\":false,\"userInteractionRequired\":false}]},\"weaknesses\":[{\"source\":\"ics-cert@hq.dhs.gov\",\"type\":\"Secondary\",\"description\":[{\"lang\":\"en\",\"value\":\"CWE-603\"}]},{\"source\":\"nvd@nist.gov\",\"type\":\"Primary\",\"description\":[{\"lang\":\"en\",\"value\":\"CWE-287\"}]}],\"configurations\":[{\"operator\":\"AND\",\"nodes\":[{\"operator\":\"OR\",\"negate\":false,\"cpeMatch\":[{\"vulnerable\":true,\"criteria\":\"cpe:2.3:o:rockwellautomation:micrologix_1400_a_firmware:*:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"614FFE85-E795-4590-B83D-87D759BA2AE8\"},{\"vulnerable\":true,\"criteria\":\"cpe:2.3:o:rockwellautomation:micrologix_1400_b_firmware:*:*:*:*:*:*:*:*\",\"versionEndIncluding\":\"21.001\",\"matchCriteriaId\":\"344EE9F6-1E89-4BCA-BDED-800F274D7845\"}]},{\"operator\":\"OR\",\"negate\":false,\"cpeMatch\":[{\"vulnerable\":false,\"criteria\":\"cpe:2.3:h:rockwellautomation:micrologix_1400:-:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"196EA0BE-FDF3-46BE-B3DA-5F49208C5D80\"}]}]},{\"operator\":\"AND\",\"nodes\":[{\"operator\":\"OR\",\"negate\":false,\"cpeMatch\":[{\"vulnerable\":true,\"criteria\":\"cpe:2.3:o:rockwellautomation:micrologix_1100_firmware:*:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"D5252A0C-A923-4BA0-A857-9BF21F8BF79B\"}]},{\"operator\":\"OR\",\"negate\":false,\"cpeMatch\":[{\"vulnerable\":false,\"criteria\":\"cpe:2.3:h:rockwellautomation:micrologix_1100:-:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"DA42C7F4-EEC1-44D2-BD46-237969FF6E1A\"}]}]},{\"nodes\":[{\"operator\":\"OR\",\"negate\":false,\"cpeMatch\":[{\"vulnerable\":true,\"criteria\":\"cpe:2.3:a:rockwellautomation:rslogix_500:*:*:*:*:*:*:*:*\",\"versionEndIncluding\":\"12.001\",\"matchCriteriaId\":\"F8A9694E-1C9E-4DF4-B91F-753A5FB4CDD6\"}]}]}],\"references\":[{\"url\":\"https://www.us-cert.gov/ics/advisories/icsa-20-070-06\",\"source\":\"ics-cert@hq.dhs.gov\",\"tags\":[\"Third Party Advisory\",\"US Government Resource\"]},{\"url\":\"https://www.us-cert.gov/ics/advisories/icsa-20-070-06\",\"source\":\"af854a3a-2127-422b-91ae-364da2661108\",\"tags\":[\"Third Party Advisory\",\"US Government Resource\"]}]}}"
  }
}


Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Sightings

Author Source Type Date

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
  • Confirmed: The vulnerability is confirmed from an analyst perspective.
  • Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
  • Patched: This vulnerability was successfully patched by the user reporting the sighting.
  • Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
  • Not confirmed: The user expresses doubt about the veracity of the vulnerability.
  • Not patched: This vulnerability was not successfully patched by the user reporting the sighting.


Loading…

Loading…