SSA-128393: Firmware Decryption Vulnerability in SICAM A8000 CP-8031 and CP-8050
Notes
Summary
The SICAM A8000 CP-8031 and CP-8050 devices are affected by a vulnerability that could allow an attacker with physical access to the device to decrypt the firmware.
Siemens has released new firmware and hardware versions for the affected products and recommends to update to the latest versions.
Both the firmware and the hardware update are required to fix the vulnerability. For details see the section "Additional Information".
General Recommendations
Operators of critical power systems (e.g. TSOs or DSOs) worldwide are usually required by regulations to build resilience into the power grids by applying multi-level redundant secondary protection schemes. It is therefore recommended that the operators check whether appropriate resilient protection measures are in place. The risk of cyber incidents impacting the grid's reliability can thus be minimized by virtue of the grid design.
Siemens strongly recommends applying the provided security updates using the corresponding tooling and documented procedures made available with the product. If supported by the product, an automated means to apply the security updates across multiple product instances may be used. Siemens strongly recommends prior validation of any security update before being applied, and supervision by trained staff of the update process in the target environment.
As a general security measure Siemens strongly recommends to protect network access with appropriate mechanisms (e.g. firewalls, segmentation, VPN). It is advised to configure the environment according to our operational guidelines in order to run the devices in a protected IT environment.
Recommended security guidelines can be found at:
https://www.siemens.com/gridsecurity
Additional Resources
For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories
Terms of Use
The use of Siemens Security Advisories is subject to the terms and conditions listed on: https://www.siemens.com/productcert/terms-of-use.
{
"document": {
"category": "csaf_security_advisory",
"csaf_version": "2.0",
"distribution": {
"text": "Disclosure is not limited. (TLPv2: TLP:CLEAR)",
"tlp": {
"label": "WHITE"
}
},
"lang": "en",
"notes": [
{
"category": "summary",
"text": "The SICAM A8000 CP-8031 and CP-8050 devices are affected by a vulnerability that could allow an attacker with physical access to the device to decrypt the firmware.\n\nSiemens has released new firmware and hardware versions for the affected products and recommends to update to the latest versions.\nBoth the firmware and the hardware update are required to fix the vulnerability. For details see the section \"Additional Information\".",
"title": "Summary"
},
{
"category": "general",
"text": "Operators of critical power systems (e.g. TSOs or DSOs) worldwide are usually required by regulations to build resilience into the power grids by applying multi-level redundant secondary protection schemes. It is therefore recommended that the operators check whether appropriate resilient protection measures are in place. The risk of cyber incidents impacting the grid\u0027s reliability can thus be minimized by virtue of the grid design.\nSiemens strongly recommends applying the provided security updates using the corresponding tooling and documented procedures made available with the product. If supported by the product, an automated means to apply the security updates across multiple product instances may be used. Siemens strongly recommends prior validation of any security update before being applied, and supervision by trained staff of the update process in the target environment. \nAs a general security measure Siemens strongly recommends to protect network access with appropriate mechanisms (e.g. firewalls, segmentation, VPN). It is advised to configure the environment according to our operational guidelines in order to run the devices in a protected IT environment.\n\nRecommended security guidelines can be found at:\n\nhttps://www.siemens.com/gridsecurity",
"title": "General Recommendations"
},
{
"category": "general",
"text": "For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories",
"title": "Additional Resources"
},
{
"category": "legal_disclaimer",
"text": "The use of Siemens Security Advisories is subject to the terms and conditions listed on: https://www.siemens.com/productcert/terms-of-use.",
"title": "Terms of Use"
}
],
"publisher": {
"category": "vendor",
"contact_details": "productcert@siemens.com",
"name": "Siemens ProductCERT",
"namespace": "https://www.siemens.com"
},
"references": [
{
"category": "self",
"summary": "SSA-128393: Firmware Decryption Vulnerability in SICAM A8000 CP-8031 and CP-8050 - HTML Version",
"url": "https://cert-portal.siemens.com/productcert/html/ssa-128393.html"
},
{
"category": "self",
"summary": "SSA-128393: Firmware Decryption Vulnerability in SICAM A8000 CP-8031 and CP-8050 - CSAF Version",
"url": "https://cert-portal.siemens.com/productcert/csaf/ssa-128393.json"
}
],
"title": "SSA-128393: Firmware Decryption Vulnerability in SICAM A8000 CP-8031 and CP-8050",
"tracking": {
"current_release_date": "2024-12-10T00:00:00Z",
"generator": {
"engine": {
"name": "Siemens ProductCERT CSAF Generator",
"version": "1"
}
},
"id": "SSA-128393",
"initial_release_date": "2024-12-10T00:00:00Z",
"revision_history": [
{
"date": "2024-12-10T00:00:00Z",
"legacy_version": "1.0",
"number": "1",
"summary": "Publication Date"
}
],
"status": "interim",
"version": "1"
}
},
"product_tree": {
"branches": [
{
"branches": [
{
"branches": [
{
"category": "product_version_range",
"name": "vers:all/\u003cV05.30",
"product": {
"name": "CPCI85 Central Processing/Communication",
"product_id": "1"
}
}
],
"category": "product_name",
"name": "CPCI85 Central Processing/Communication"
}
],
"category": "vendor",
"name": "Siemens"
}
]
},
"vulnerabilities": [
{
"cve": "CVE-2024-53832",
"cwe": {
"id": "CWE-522",
"name": "Insufficiently Protected Credentials"
},
"notes": [
{
"category": "summary",
"text": "The affected devices contain a secure element which is connected via an unencrypted SPI bus. This could allow an attacker with physical access to the SPI bus to observe the password used for the secure element authentication, and then use the secure element as an oracle to decrypt all encrypted update files.",
"title": "Summary"
}
],
"product_status": {
"known_affected": [
"1"
]
},
"remediations": [
{
"category": "vendor_fix",
"details": "Update to V05.30 or later version",
"product_ids": [
"1"
]
}
],
"scores": [
{
"cvss_v3": {
"baseScore": 4.6,
"baseSeverity": "MEDIUM",
"vectorString": "CVSS:3.1/AV:P/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N",
"version": "3.1"
},
"products": [
"1"
]
}
],
"title": "CVE-2024-53832"
}
]
}
Loading…
Loading…
Sightings
| Author | Source | Type | Date |
|---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
- Confirmed: The vulnerability is confirmed from an analyst perspective.
- Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
- Patched: This vulnerability was successfully patched by the user reporting the sighting.
- Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
- Not confirmed: The user expresses doubt about the veracity of the vulnerability.
- Not patched: This vulnerability was not successfully patched by the user reporting the sighting.
Loading…
Loading…