Action not permitted
Modal body text goes here.
Modal Title
Modal Body
ssa-570294
Vulnerability from csaf_siemens
Published
2022-11-08 00:00
Modified
2024-01-09 00:00
Summary
SSA-570294: Multiple Vulnerabilities in SICAM Q100 Before V2.50
Notes
Summary
SICAM Q100 devices contain multiple vulnerabilities that could allow an attacker to take over the session of a logged in user or to inject custom code.
Siemens has released updates for the affected products and recommends to update to the latest versions.
General Recommendations
Operators of critical power systems (e.g. TSOs or DSOs) worldwide are usually required by regulations to build resilience into the power grids by applying multi-level redundant secondary protection schemes. It is therefore recommended that the operators check whether appropriate resilient protection measures are in place. The risk of cyber incidents impacting the grid's reliability can thus be minimized by virtue of the grid design.
Siemens strongly recommends applying the provided security updates using the corresponding tooling and documented procedures made available with the product. If supported by the product, an automated means to apply the security updates across multiple product instances may be used. Siemens strongly recommends prior validation of any security update before being applied, and supervision by trained staff of the update process in the target environment.
As a general security measure Siemens strongly recommends to protect network access with appropriate mechanisms (e.g. firewalls, segmentation, VPN). It is advised to configure the environment according to our operational guidelines in order to run the devices in a protected IT environment.
Recommended security guidelines can be found at:
https://www.siemens.com/gridsecurity
Additional Resources
For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories
Terms of Use
Siemens Security Advisories are subject to the terms and conditions contained in Siemens' underlying license terms or other applicable agreements previously agreed to with Siemens (hereinafter "License Terms"). To the extent applicable to information, software or documentation made available in or through a Siemens Security Advisory, the Terms of Use of Siemens' Global Website (https://www.siemens.com/terms_of_use, hereinafter "Terms of Use"), in particular Sections 8-10 of the Terms of Use, shall apply additionally. In case of conflicts, the License Terms shall prevail over the Terms of Use.
{ "document": { "category": "csaf_security_advisory", "csaf_version": "2.0", "distribution": { "text": "Disclosure is not limited. (TLPv2: TLP:CLEAR)", "tlp": { "label": "WHITE" } }, "lang": "en", "notes": [ { "category": "summary", "text": "SICAM Q100 devices contain multiple vulnerabilities that could allow an attacker to take over the session of a logged in user or to inject custom code.\n\nSiemens has released updates for the affected products and recommends to update to the latest versions.", "title": "Summary" }, { "category": "general", "text": "Operators of critical power systems (e.g. TSOs or DSOs) worldwide are usually required by regulations to build resilience into the power grids by applying multi-level redundant secondary protection schemes. It is therefore recommended that the operators check whether appropriate resilient protection measures are in place. The risk of cyber incidents impacting the grid\u0027s reliability can thus be minimized by virtue of the grid design.\nSiemens strongly recommends applying the provided security updates using the corresponding tooling and documented procedures made available with the product. If supported by the product, an automated means to apply the security updates across multiple product instances may be used. Siemens strongly recommends prior validation of any security update before being applied, and supervision by trained staff of the update process in the target environment. \nAs a general security measure Siemens strongly recommends to protect network access with appropriate mechanisms (e.g. firewalls, segmentation, VPN). It is advised to configure the environment according to our operational guidelines in order to run the devices in a protected IT environment.\n\nRecommended security guidelines can be found at:\n\nhttps://www.siemens.com/gridsecurity", "title": "General Recommendations" }, { "category": "general", "text": "For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories", "title": "Additional Resources" }, { "category": "legal_disclaimer", "text": "Siemens Security Advisories are subject to the terms and conditions contained in Siemens\u0027 underlying license terms or other applicable agreements previously agreed to with Siemens (hereinafter \"License Terms\"). To the extent applicable to information, software or documentation made available in or through a Siemens Security Advisory, the Terms of Use of Siemens\u0027 Global Website (https://www.siemens.com/terms_of_use, hereinafter \"Terms of Use\"), in particular Sections 8-10 of the Terms of Use, shall apply additionally. In case of conflicts, the License Terms shall prevail over the Terms of Use.", "title": "Terms of Use" } ], "publisher": { "category": "vendor", "contact_details": "productcert@siemens.com", "name": "Siemens ProductCERT", "namespace": "https://www.siemens.com" }, "references": [ { "category": "self", "summary": "SSA-570294: Multiple Vulnerabilities in SICAM Q100 Before V2.50 - HTML Version", "url": "https://cert-portal.siemens.com/productcert/html/ssa-570294.html" }, { "category": "self", "summary": "SSA-570294: Multiple Vulnerabilities in SICAM Q100 Before V2.50 - CSAF Version", "url": "https://cert-portal.siemens.com/productcert/csaf/ssa-570294.json" }, { "category": "self", "summary": "SSA-570294: Multiple Vulnerabilities in SICAM Q100 Before V2.50 - PDF Version", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-570294.pdf" }, { "category": "self", "summary": "SSA-570294: Multiple Vulnerabilities in SICAM Q100 Before V2.50 - TXT Version", "url": "https://cert-portal.siemens.com/productcert/txt/ssa-570294.txt" } ], "title": "SSA-570294: Multiple Vulnerabilities in SICAM Q100 Before V2.50", "tracking": { "current_release_date": "2024-01-09T00:00:00Z", "generator": { "engine": { "name": "Siemens ProductCERT CSAF Generator", "version": "1" } }, "id": "SSA-570294", "initial_release_date": "2022-11-08T00:00:00Z", "revision_history": [ { "date": "2022-11-08T00:00:00Z", "legacy_version": "1.0", "number": "1", "summary": "Publication Date" }, { "date": "2024-01-09T00:00:00Z", "legacy_version": "1.1", "number": "2", "summary": "Added legacy Q100 device models (-0AA1) which are also affected and provide the same fix version" } ], "status": "interim", "version": "2" } }, "product_tree": { "branches": [ { "branches": [ { "branches": [ { "category": "product_version_range", "name": "\u003cV2.50", "product": { "name": "POWER METER SICAM Q100 (7KG9501-0AA01-0AA1)", "product_id": "1", "product_identification_helper": { "model_numbers": [ "7KG9501-0AA01-0AA1" ] } } } ], "category": "product_name", "name": "POWER METER SICAM Q100 (7KG9501-0AA01-0AA1)" }, { "branches": [ { "category": "product_version_range", "name": "\u003cV2.50", "product": { "name": "POWER METER SICAM Q100 (7KG9501-0AA01-2AA1)", "product_id": "2", "product_identification_helper": { "model_numbers": [ "7KG9501-0AA01-2AA1" ] } } } ], "category": "product_name", "name": "POWER METER SICAM Q100 (7KG9501-0AA01-2AA1)" }, { "branches": [ { "category": "product_version_range", "name": "\u003cV2.50", "product": { "name": "POWER METER SICAM Q100 (7KG9501-0AA31-0AA1)", "product_id": "3", "product_identification_helper": { "model_numbers": [ "7KG9501-0AA31-0AA1" ] } } } ], "category": "product_name", "name": "POWER METER SICAM Q100 (7KG9501-0AA31-0AA1)" }, { "branches": [ { "category": "product_version_range", "name": "\u003cV2.50", "product": { "name": "POWER METER SICAM Q100 (7KG9501-0AA31-2AA1)", "product_id": "4", "product_identification_helper": { "model_numbers": [ "7KG9501-0AA31-2AA1" ] } } } ], "category": "product_name", "name": "POWER METER SICAM Q100 (7KG9501-0AA31-2AA1)" } ], "category": "vendor", "name": "Siemens" } ] }, "vulnerabilities": [ { "cve": "CVE-2022-43398", "cwe": { "id": "CWE-384", "name": "Session Fixation" }, "notes": [ { "category": "summary", "text": "Affected devices do not renew the session cookie after login/logout and also accept user defined session cookies. An attacker could overwrite the stored session cookie of a user. After the victim logged in, the attacker is given access to the user\u0027s account through the activated session.", "title": "Summary" } ], "product_status": { "known_affected": [ "1", "2", "3", "4" ] }, "remediations": [ { "category": "vendor_fix", "details": "Update to V2.50 or later version", "product_ids": [ "1", "2", "3", "4" ] }, { "category": "workaround", "details": "Restrict access to port 443/tcp to trusted IP addresses only", "product_ids": [ "1", "2", "3", "4" ] } ], "scores": [ { "cvss_v3": { "baseScore": 7.5, "baseSeverity": "HIGH", "vectorString": "CVSS:3.1/AV:N/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C", "version": "3.1" }, "products": [ "4", "3", "1", "2" ] } ], "title": "CVE-2022-43398" }, { "cve": "CVE-2022-43439", "cwe": { "id": "CWE-20", "name": "Improper Input Validation" }, "notes": [ { "category": "summary", "text": "Affected devices do not properly validate the Language-parameter in requests to the web interface on port 443/tcp. This could allow an authenticated remote attacker to crash the device (followed by an automatic reboot) or to execute arbitrary code on the device.", "title": "Summary" } ], "product_status": { "known_affected": [ "1", "2", "3", "4" ] }, "remediations": [ { "category": "vendor_fix", "details": "Update to V2.50 or later version", "product_ids": [ "1", "2", "3", "4" ] }, { "category": "workaround", "details": "Restrict access to port 443/tcp to trusted IP addresses only", "product_ids": [ "1", "2", "3", "4" ] } ], "scores": [ { "cvss_v3": { "baseScore": 9.9, "baseSeverity": "CRITICAL", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:C/C:H/I:H/A:H/E:P/RL:O/RC:C", "version": "3.1" }, "products": [ "4", "3", "1", "2" ] } ], "title": "CVE-2022-43439" }, { "cve": "CVE-2022-43545", "cwe": { "id": "CWE-20", "name": "Improper Input Validation" }, "notes": [ { "category": "summary", "text": "Affected devices do not properly validate the RecordType-parameter in requests to the web interface on port 443/tcp. This could allow an authenticated remote attacker to crash the device (followed by an automatic reboot) or to execute arbitrary code on the device.", "title": "Summary" } ], "product_status": { "known_affected": [ "1", "2", "3", "4" ] }, "remediations": [ { "category": "vendor_fix", "details": "Update to V2.50 or later version", "product_ids": [ "1", "2", "3", "4" ] }, { "category": "workaround", "details": "Restrict access to port 443/tcp to trusted IP addresses only", "product_ids": [ "1", "2", "3", "4" ] } ], "scores": [ { "cvss_v3": { "baseScore": 9.9, "baseSeverity": "CRITICAL", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:C/C:H/I:H/A:H/E:P/RL:O/RC:C", "version": "3.1" }, "products": [ "4", "3", "1", "2" ] } ], "title": "CVE-2022-43545" }, { "cve": "CVE-2022-43546", "cwe": { "id": "CWE-20", "name": "Improper Input Validation" }, "notes": [ { "category": "summary", "text": "Affected devices do not properly validate the EndTime-parameter in requests to the web interface on port 443/tcp. This could allow an authenticated remote attacker to crash the device (followed by an automatic reboot) or to execute arbitrary code on the device.", "title": "Summary" } ], "product_status": { "known_affected": [ "1", "2", "3", "4" ] }, "remediations": [ { "category": "vendor_fix", "details": "Update to V2.50 or later version", "product_ids": [ "1", "2", "3", "4" ] }, { "category": "workaround", "details": "Restrict access to port 443/tcp to trusted IP addresses only", "product_ids": [ "1", "2", "3", "4" ] } ], "scores": [ { "cvss_v3": { "baseScore": 9.9, "baseSeverity": "CRITICAL", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:C/C:H/I:H/A:H/E:P/RL:O/RC:C", "version": "3.1" }, "products": [ "4", "3", "1", "2" ] } ], "title": "CVE-2022-43546" } ] }
CVE-2022-43546 (GCVE-0-2022-43546)
Vulnerability from cvelistv5
Published
2022-11-08 00:00
Modified
2024-10-21 16:08
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-20 - Improper Input Validation
Summary
A vulnerability has been identified in POWER METER SICAM Q100 (All versions < V2.50), POWER METER SICAM Q100 (All versions < V2.50), POWER METER SICAM Q100 (All versions < V2.50), POWER METER SICAM Q100 (All versions < V2.50), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10). Affected devices do not properly validate the EndTime-parameter in requests to the web interface on port 443/tcp. This could allow an authenticated remote attacker to crash the device (followed by an automatic reboot) or to execute arbitrary code on the device.
References
Impacted products
Vendor | Product | Version | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
► | Siemens | POWER METER SICAM Q100 |
Version: All versions < V2.50 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-03T13:32:59.647Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-572005.pdf" }, { "tags": [ "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-570294.pdf" }, { "tags": [ "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-887249.pdf" } ], "title": "CVE Program Container" }, { "affected": [ { "cpes": [ "cpe:2.3:o:siemens:sicam_q100_firmware:*:*:*:*:*:*:*:*" ], "defaultStatus": "unknown", "product": "sicam_q100_firmware", "vendor": "siemens", "versions": [ { "lessThan": "2.50", "status": "affected", "version": "0", "versionType": "custom" } ] }, { "cpes": [ "cpe:2.3:o:siemens:sicam_p850_firmware:*:*:*:*:*:*:*:*" ], "defaultStatus": "unknown", "product": "sicam_p850_firmware", "vendor": "siemens", "versions": [ { "lessThan": "3.10", "status": "affected", "version": "0", "versionType": "custom" } ] }, { "cpes": [ "cpe:2.3:o:siemens:sicam_p855_firmware:*:*:*:*:*:*:*:*" ], "defaultStatus": "unknown", "product": "sicam_p855_firmware", "vendor": "siemens", "versions": [ { "lessThan": "3.10", "status": "affected", "version": "0", "versionType": "custom" } ] } ], "metrics": [ { "other": { "content": { "id": "CVE-2022-43546", "options": [ { "Exploitation": "none" }, { "Automatable": "no" }, { "Technical Impact": "total" } ], "role": "CISA Coordinator", "timestamp": "2024-10-15T17:16:01.044378Z", "version": "2.0.3" }, "type": "ssvc" } } ], "providerMetadata": { "dateUpdated": "2024-10-21T16:08:33.311Z", "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0", "shortName": "CISA-ADP" }, "title": "CISA ADP Vulnrichment" } ], "cna": { "affected": [ { "defaultStatus": "unknown", "product": "POWER METER SICAM Q100", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V2.50" } ] }, { "defaultStatus": "unknown", "product": "POWER METER SICAM Q100", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V2.50" } ] }, { "defaultStatus": "unknown", "product": "POWER METER SICAM Q100", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V2.50" } ] }, { "defaultStatus": "unknown", "product": "POWER METER SICAM Q100", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V2.50" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in POWER METER SICAM Q100 (All versions \u003c V2.50), POWER METER SICAM Q100 (All versions \u003c V2.50), POWER METER SICAM Q100 (All versions \u003c V2.50), POWER METER SICAM Q100 (All versions \u003c V2.50), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10). Affected devices do not properly validate the EndTime-parameter in requests to the web interface on port 443/tcp. This could allow an authenticated remote attacker to crash the device (followed by an automatic reboot) or to execute arbitrary code on the device." } ], "metrics": [ { "cvssV3_1": { "baseScore": 9.9, "baseSeverity": "CRITICAL", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:C/C:H/I:H/A:H/E:P/RL:O/RC:C", "version": "3.1" } } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-20", "description": "CWE-20: Improper Input Validation", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2024-01-09T09:58:41.480Z", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-572005.pdf" }, { "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-570294.pdf" }, { "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-887249.pdf" } ] } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2022-43546", "datePublished": "2022-11-08T00:00:00", "dateReserved": "2022-10-20T00:00:00", "dateUpdated": "2024-10-21T16:08:33.311Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2022-43545 (GCVE-0-2022-43545)
Vulnerability from cvelistv5
Published
2022-11-08 00:00
Modified
2024-08-03 13:32
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-20 - Improper Input Validation
Summary
A vulnerability has been identified in POWER METER SICAM Q100 (All versions < V2.50), POWER METER SICAM Q100 (All versions < V2.50), POWER METER SICAM Q100 (All versions < V2.50), POWER METER SICAM Q100 (All versions < V2.50), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10). Affected devices do not properly validate the RecordType-parameter in requests to the web interface on port 443/tcp. This could allow an authenticated remote attacker to crash the device (followed by an automatic reboot) or to execute arbitrary code on the device.
References
Impacted products
Vendor | Product | Version | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
► | Siemens | POWER METER SICAM Q100 |
Version: All versions < V2.50 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-03T13:32:59.727Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-572005.pdf" }, { "tags": [ "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-570294.pdf" }, { "tags": [ "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-887249.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "defaultStatus": "unknown", "product": "POWER METER SICAM Q100", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V2.50" } ] }, { "defaultStatus": "unknown", "product": "POWER METER SICAM Q100", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V2.50" } ] }, { "defaultStatus": "unknown", "product": "POWER METER SICAM Q100", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V2.50" } ] }, { "defaultStatus": "unknown", "product": "POWER METER SICAM Q100", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V2.50" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in POWER METER SICAM Q100 (All versions \u003c V2.50), POWER METER SICAM Q100 (All versions \u003c V2.50), POWER METER SICAM Q100 (All versions \u003c V2.50), POWER METER SICAM Q100 (All versions \u003c V2.50), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10). Affected devices do not properly validate the RecordType-parameter in requests to the web interface on port 443/tcp. This could allow an authenticated remote attacker to crash the device (followed by an automatic reboot) or to execute arbitrary code on the device." } ], "metrics": [ { "cvssV3_1": { "baseScore": 9.9, "baseSeverity": "CRITICAL", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:C/C:H/I:H/A:H/E:P/RL:O/RC:C", "version": "3.1" } } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-20", "description": "CWE-20: Improper Input Validation", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2024-01-09T09:58:12.217Z", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-572005.pdf" }, { "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-570294.pdf" }, { "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-887249.pdf" } ] } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2022-43545", "datePublished": "2022-11-08T00:00:00", "dateReserved": "2022-10-20T00:00:00", "dateUpdated": "2024-08-03T13:32:59.727Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2022-43439 (GCVE-0-2022-43439)
Vulnerability from cvelistv5
Published
2022-11-08 00:00
Modified
2024-08-03 13:32
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-20 - Improper Input Validation
Summary
A vulnerability has been identified in POWER METER SICAM Q100 (All versions < V2.50), POWER METER SICAM Q100 (All versions < V2.50), POWER METER SICAM Q100 (All versions < V2.50), POWER METER SICAM Q100 (All versions < V2.50), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P850 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10), SICAM P855 (All versions < V3.10). Affected devices do not properly validate the Language-parameter in requests to the web interface on port 443/tcp. This could allow an authenticated remote attacker to crash the device (followed by an automatic reboot) or to execute arbitrary code on the device.
References
Impacted products
Vendor | Product | Version | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
► | Siemens | POWER METER SICAM Q100 |
Version: All versions < V2.50 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-03T13:32:59.174Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-572005.pdf" }, { "tags": [ "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-570294.pdf" }, { "tags": [ "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-887249.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "defaultStatus": "unknown", "product": "POWER METER SICAM Q100", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V2.50" } ] }, { "defaultStatus": "unknown", "product": "POWER METER SICAM Q100", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V2.50" } ] }, { "defaultStatus": "unknown", "product": "POWER METER SICAM Q100", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V2.50" } ] }, { "defaultStatus": "unknown", "product": "POWER METER SICAM Q100", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V2.50" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P850", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] }, { "defaultStatus": "unknown", "product": "SICAM P855", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.10" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in POWER METER SICAM Q100 (All versions \u003c V2.50), POWER METER SICAM Q100 (All versions \u003c V2.50), POWER METER SICAM Q100 (All versions \u003c V2.50), POWER METER SICAM Q100 (All versions \u003c V2.50), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P850 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10), SICAM P855 (All versions \u003c V3.10). Affected devices do not properly validate the Language-parameter in requests to the web interface on port 443/tcp. This could allow an authenticated remote attacker to crash the device (followed by an automatic reboot) or to execute arbitrary code on the device." } ], "metrics": [ { "cvssV3_1": { "baseScore": 9.9, "baseSeverity": "CRITICAL", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:C/C:H/I:H/A:H/E:P/RL:O/RC:C", "version": "3.1" } } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-20", "description": "CWE-20: Improper Input Validation", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2024-01-09T09:57:43.953Z", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-572005.pdf" }, { "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-570294.pdf" }, { "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-887249.pdf" } ] } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2022-43439", "datePublished": "2022-11-08T00:00:00", "dateReserved": "2022-10-19T00:00:00", "dateUpdated": "2024-08-03T13:32:59.174Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2022-43398 (GCVE-0-2022-43398)
Vulnerability from cvelistv5
Published
2022-11-08 00:00
Modified
2024-08-03 13:32
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-384 - Session Fixation
Summary
A vulnerability has been identified in POWER METER SICAM Q100 (All versions < V2.50), POWER METER SICAM Q100 (All versions < V2.50), POWER METER SICAM Q100 (All versions < V2.50), POWER METER SICAM Q100 (All versions < V2.50). Affected devices do not renew the session cookie after login/logout and also accept user defined session cookies. An attacker could overwrite the stored session cookie of a user. After the victim logged in, the attacker is given access to the user's account through the activated session.
References
Impacted products
Vendor | Product | Version | |||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
► | Siemens | POWER METER SICAM Q100 |
Version: All versions < V2.50 |
||||||||||||||||
|
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-03T13:32:58.148Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-570294.pdf" }, { "tags": [ "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-887249.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "defaultStatus": "unknown", "product": "POWER METER SICAM Q100", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V2.50" } ] }, { "defaultStatus": "unknown", "product": "POWER METER SICAM Q100", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V2.50" } ] }, { "defaultStatus": "unknown", "product": "POWER METER SICAM Q100", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V2.50" } ] }, { "defaultStatus": "unknown", "product": "POWER METER SICAM Q100", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V2.50" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in POWER METER SICAM Q100 (All versions \u003c V2.50), POWER METER SICAM Q100 (All versions \u003c V2.50), POWER METER SICAM Q100 (All versions \u003c V2.50), POWER METER SICAM Q100 (All versions \u003c V2.50). Affected devices do not renew the session cookie after login/logout and also accept user defined session cookies. An attacker could overwrite the stored session cookie of a user. After the victim logged in, the attacker is given access to the user\u0027s account through the activated session." } ], "metrics": [ { "cvssV3_1": { "baseScore": 7.5, "baseSeverity": "HIGH", "vectorString": "CVSS:3.1/AV:N/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C", "version": "3.1" } } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-384", "description": "CWE-384: Session Fixation", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2024-01-09T09:57:13.900Z", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-570294.pdf" }, { "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-887249.pdf" } ] } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2022-43398", "datePublished": "2022-11-08T00:00:00", "dateReserved": "2022-10-18T00:00:00", "dateUpdated": "2024-08-03T13:32:58.148Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
Loading…
Loading…
Sightings
Author | Source | Type | Date |
---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
- Confirmed: The vulnerability is confirmed from an analyst perspective.
- Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
- Patched: This vulnerability was successfully patched by the user reporting the sighting.
- Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
- Not confirmed: The user expresses doubt about the veracity of the vulnerability.
- Not patched: This vulnerability was not successfully patched by the user reporting the sighting.
Loading…
Loading…