ghsa-7934-59fw-r79m
Vulnerability from github
Rockwell Automation RSLinx Enterprise Software (LogReceiver.exe) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 does not handle input correctly and results in a logic error if it calculates an incorrect value for the “End of Current Record” field. By sending a datagram to the service over Port 4444/UDP with the “Record Data Size” field modified to a specifically oversized value, the service will calculate an undersized value for the “Total Record Size.” Then the service will calculate an incorrect value for the “End of Current Record” field causing access violations that lead to a service crash. The service can be recovered with a manual reboot. The patches and details pertaining to these vulnerabilities can be found at the following Rockwell Automation security advisory link (login is required): https://rockwellautomation.custhelp.com/app/answers/detail/a_id/537599
{ "affected": [], "aliases": [ "CVE-2013-2806" ], "database_specific": { "cwe_ids": [ "CWE-190" ], "github_reviewed": false, "github_reviewed_at": null, "nvd_published_at": "2019-03-26T17:29:00Z", "severity": "HIGH" }, "details": "Rockwell Automation RSLinx Enterprise Software (LogReceiver.exe) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 does not handle input correctly and results in a logic error if it calculates an incorrect value for the \u201cEnd of Current Record\u201d field. By sending a datagram to the service over Port 4444/UDP with the \u201cRecord Data Size\u201d field modified to a specifically oversized value, the service will calculate an undersized value for the \u201cTotal Record Size.\u201d Then the service will calculate an incorrect value for the \u201cEnd of Current Record\u201d field causing access violations that lead to a service crash. The service can be recovered with a manual reboot. The patches and details pertaining to these vulnerabilities can be found at the following Rockwell Automation security advisory link (login is required): https://rockwellautomation.custhelp.com/app/answers/detail/a_id/537599", "id": "GHSA-7934-59fw-r79m", "modified": "2022-05-13T01:28:30Z", "published": "2022-05-13T01:28:30Z", "references": [ { "type": "ADVISORY", "url": "https://nvd.nist.gov/vuln/detail/CVE-2013-2806" }, { "type": "WEB", "url": "https://ics-cert.us-cert.gov/advisories/ICSA-13-095-02" } ], "schema_version": "1.4.0", "severity": [ { "score": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H", "type": "CVSS_V3" } ] }
Sightings
Author | Source | Type | Date |
---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
- Confirmed: The vulnerability is confirmed from an analyst perspective.
- Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
- Patched: This vulnerability was successfully patched by the user reporting the sighting.
- Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
- Not confirmed: The user expresses doubt about the veracity of the vulnerability.
- Not patched: This vulnerability was not successfully patched by the user reporting the sighting.