ssa-614723
Vulnerability from csaf_siemens
Published
2025-05-13 00:00
Modified
2025-07-08 00:00
Summary
SSA-614723: Denial of Service Vulnerabilities in User Management Component (UMC)
Notes
Summary
Siemens User Management Component (UMC) is affected by three vulnerabilities which could allow an unauthenticated remote attacker to cause a denial of service condition.
Siemens has released new versions for several affected products and recommends to update to the latest versions. Siemens is preparing further fix versions and recommends specific countermeasures for products where fixes are not, or not yet available.
General Recommendations
As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens' operational guidelines for Industrial Security (Download:
https://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.
Additional information on Industrial Security by Siemens can be found at: https://www.siemens.com/industrialsecurity
Additional Resources
For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories
Terms of Use
The use of Siemens Security Advisories is subject to the terms and conditions listed on: https://www.siemens.com/productcert/terms-of-use.
{ "document": { "category": "csaf_security_advisory", "csaf_version": "2.0", "distribution": { "text": "Disclosure is not limited. (TLPv2: TLP:CLEAR)", "tlp": { "label": "WHITE" } }, "lang": "en", "notes": [ { "category": "summary", "text": "Siemens User Management Component (UMC) is affected by three vulnerabilities which could allow an unauthenticated remote attacker to cause a denial of service condition.\n\nSiemens has released new versions for several affected products and recommends to update to the latest versions. Siemens is preparing further fix versions and recommends specific countermeasures for products where fixes are not, or not yet available.", "title": "Summary" }, { "category": "general", "text": "As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens\u0027 operational guidelines for Industrial Security (Download: \nhttps://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.\nAdditional information on Industrial Security by Siemens can be found at: https://www.siemens.com/industrialsecurity", "title": "General Recommendations" }, { "category": "general", "text": "For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories", "title": "Additional Resources" }, { "category": "legal_disclaimer", "text": "The use of Siemens Security Advisories is subject to the terms and conditions listed on: https://www.siemens.com/productcert/terms-of-use.", "title": "Terms of Use" } ], "publisher": { "category": "vendor", "contact_details": "productcert@siemens.com", "name": "Siemens ProductCERT", "namespace": "https://www.siemens.com" }, "references": [ { "category": "self", "summary": "SSA-614723: Denial of Service Vulnerabilities in User Management Component (UMC) - HTML Version", "url": "https://cert-portal.siemens.com/productcert/html/ssa-614723.html" }, { "category": "self", "summary": "SSA-614723: Denial of Service Vulnerabilities in User Management Component (UMC) - CSAF Version", "url": "https://cert-portal.siemens.com/productcert/csaf/ssa-614723.json" } ], "title": "SSA-614723: Denial of Service Vulnerabilities in User Management Component (UMC)", "tracking": { "current_release_date": "2025-07-08T00:00:00Z", "generator": { "engine": { "name": "Siemens ProductCERT CSAF Generator", "version": "1" } }, "id": "SSA-614723", "initial_release_date": "2025-05-13T00:00:00Z", "revision_history": [ { "date": "2025-05-13T00:00:00Z", "legacy_version": "1.0", "number": "1", "summary": "Publication Date" }, { "date": "2025-07-08T00:00:00Z", "legacy_version": "1.1", "number": "2", "summary": "Added fix for SINEC NMS V4.0" } ], "status": "interim", "version": "2" } }, "product_tree": { "branches": [ { "branches": [ { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "SIMATIC PCS neo V4.1", "product_id": "1" } } ], "category": "product_name", "name": "SIMATIC PCS neo V4.1" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "SIMATIC PCS neo V5.0", "product_id": "2" } } ], "category": "product_name", "name": "SIMATIC PCS neo V5.0" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/\u003cV4.0", "product": { "name": "SINEC NMS", "product_id": "3" } } ], "category": "product_name", "name": "SINEC NMS" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "SINEMA Remote Connect", "product_id": "4" } } ], "category": "product_name", "name": "SINEMA Remote Connect" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "Totally Integrated Automation Portal (TIA Portal) V17", "product_id": "5" } } ], "category": "product_name", "name": "Totally Integrated Automation Portal (TIA Portal) V17" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "Totally Integrated Automation Portal (TIA Portal) V18", "product_id": "6" } } ], "category": "product_name", "name": "Totally Integrated Automation Portal (TIA Portal) V18" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "Totally Integrated Automation Portal (TIA Portal) V19", "product_id": "7" } } ], "category": "product_name", "name": "Totally Integrated Automation Portal (TIA Portal) V19" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "Totally Integrated Automation Portal (TIA Portal) V20", "product_id": "8" } } ], "category": "product_name", "name": "Totally Integrated Automation Portal (TIA Portal) V20" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/\u003cV2.15.1.1", "product": { "name": "User Management Component (UMC)", "product_id": "9" } } ], "category": "product_name", "name": "User Management Component (UMC)" } ], "category": "vendor", "name": "Siemens" } ] }, "vulnerabilities": [ { "cve": "CVE-2025-30174", "cwe": { "id": "CWE-125", "name": "Out-of-bounds Read" }, "notes": [ { "category": "summary", "text": "Affected products contain a out of bound read buffer overflow vulnerability in the integrated UMC component. This could allow an unauthenticated remote attacker to cause a denial of service condition.", "title": "Summary" } ], "product_status": { "known_affected": [ "1", "2", "3", "4", "5", "6", "7", "8", "9" ] }, "remediations": [ { "category": "mitigation", "details": "In non-networked scenarios/deployments block TCP ports 4002 and 4004 on machines with UMC installed. In addition if no RT server machines are used, port 4004 can be blocked completely", "product_ids": [ "1", "2", "3", "4", "5", "6", "7", "8", "9" ] }, { "category": "no_fix_planned", "details": "Currently no fix is planned", "product_ids": [ "1" ] }, { "category": "none_available", "details": "Currently no fix is available", "product_ids": [ "2" ] }, { "category": "vendor_fix", "details": "Update to V2.15.1.1 or later version", "product_ids": [ "9" ], "url": "https://support.industry.siemens.com/cs/ww/en/view/109987708/" }, { "category": "vendor_fix", "details": "Update to V4.0 or later version", "product_ids": [ "3" ], "url": "https://support.industry.siemens.com/cs/ww/en/view/109989514/" }, { "category": "vendor_fix", "details": "Update UMC to V2.15.1.1 or later compatible version \nhttps://support.industry.siemens.com/cs/ww/en/view/109987708/", "product_ids": [ "4" ] }, { "category": "vendor_fix", "details": "Update UMC to V2.15.1.1 or later compatible version\n\nhttps://support.industry.siemens.com/cs/ww/en/view/109987708/", "product_ids": [ "5", "6", "7", "8" ] } ], "scores": [ { "cvss_v3": { "baseScore": 7.5, "baseSeverity": "HIGH", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H", "version": "3.1" }, "products": [ "1", "2", "3", "4", "5", "6", "7", "8", "9" ] } ], "title": "CVE-2025-30174" }, { "cve": "CVE-2025-30175", "cwe": { "id": "CWE-787", "name": "Out-of-bounds Write" }, "notes": [ { "category": "summary", "text": "Affected products contain a out of bound write buffer overflow vulnerability in the integrated UMC component. This could allow an unauthenticated remote attacker to cause a denial of service condition.", "title": "Summary" } ], "product_status": { "known_affected": [ "1", "2", "3", "4", "5", "6", "7", "8", "9" ] }, "remediations": [ { "category": "mitigation", "details": "In non-networked scenarios/deployments block TCP ports 4002 and 4004 on machines with UMC installed. In addition if no RT server machines are used, port 4004 can be blocked completely", "product_ids": [ "1", "2", "3", "4", "5", "6", "7", "8", "9" ] }, { "category": "no_fix_planned", "details": "Currently no fix is planned", "product_ids": [ "1" ] }, { "category": "none_available", "details": "Currently no fix is available", "product_ids": [ "2" ] }, { "category": "vendor_fix", "details": "Update to V2.15.1.1 or later version", "product_ids": [ "9" ], "url": "https://support.industry.siemens.com/cs/ww/en/view/109987708/" }, { "category": "vendor_fix", "details": "Update to V4.0 or later version", "product_ids": [ "3" ], "url": "https://support.industry.siemens.com/cs/ww/en/view/109989514/" }, { "category": "vendor_fix", "details": "Update UMC to V2.15.1.1 or later compatible version \nhttps://support.industry.siemens.com/cs/ww/en/view/109987708/", "product_ids": [ "4" ] }, { "category": "vendor_fix", "details": "Update UMC to V2.15.1.1 or later compatible version\n\nhttps://support.industry.siemens.com/cs/ww/en/view/109987708/", "product_ids": [ "5", "6", "7", "8" ] } ], "scores": [ { "cvss_v3": { "baseScore": 7.5, "baseSeverity": "HIGH", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H", "version": "3.1" }, "products": [ "1", "2", "3", "4", "5", "6", "7", "8", "9" ] } ], "title": "CVE-2025-30175" }, { "cve": "CVE-2025-30176", "cwe": { "id": "CWE-125", "name": "Out-of-bounds Read" }, "notes": [ { "category": "summary", "text": "Affected products contain a out of bound read buffer overflow vulnerability in the integrated UMC component. This could allow an unauthenticated remote attacker to cause a denial of service condition.", "title": "Summary" } ], "product_status": { "known_affected": [ "1", "2", "3", "4", "5", "6", "7", "8", "9" ] }, "remediations": [ { "category": "mitigation", "details": "In non-networked scenarios/deployments block TCP ports 4002 and 4004 on machines with UMC installed. In addition if no RT server machines are used, port 4004 can be blocked completely", "product_ids": [ "1", "2", "3", "4", "5", "6", "7", "8", "9" ] }, { "category": "no_fix_planned", "details": "Currently no fix is planned", "product_ids": [ "1" ] }, { "category": "none_available", "details": "Currently no fix is available", "product_ids": [ "2" ] }, { "category": "vendor_fix", "details": "Update to V2.15.1.1 or later version", "product_ids": [ "9" ], "url": "https://support.industry.siemens.com/cs/ww/en/view/109987708/" }, { "category": "vendor_fix", "details": "Update to V4.0 or later version", "product_ids": [ "3" ], "url": "https://support.industry.siemens.com/cs/ww/en/view/109989514/" }, { "category": "vendor_fix", "details": "Update UMC to V2.15.1.1 or later compatible version \nhttps://support.industry.siemens.com/cs/ww/en/view/109987708/", "product_ids": [ "4" ] }, { "category": "vendor_fix", "details": "Update UMC to V2.15.1.1 or later compatible version\n\nhttps://support.industry.siemens.com/cs/ww/en/view/109987708/", "product_ids": [ "5", "6", "7", "8" ] } ], "scores": [ { "cvss_v3": { "baseScore": 7.5, "baseSeverity": "HIGH", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H", "version": "3.1" }, "products": [ "1", "2", "3", "4", "5", "6", "7", "8", "9" ] } ], "title": "CVE-2025-30176" } ] }
Loading…
Loading…
Sightings
Author | Source | Type | Date |
---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
- Confirmed: The vulnerability is confirmed from an analyst perspective.
- Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
- Patched: This vulnerability was successfully patched by the user reporting the sighting.
- Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
- Not confirmed: The user expresses doubt about the veracity of the vulnerability.
- Not patched: This vulnerability was not successfully patched by the user reporting the sighting.
Loading…
Loading…